Zeta UV Flame Detector C/W Base

Zeta UV Flame Detector C/W Base

Product code   80-045-FEUV2000
£150.00
exc. VAT
£180.00  inc. VAT


Zeta UV Flame Detector C/W Base   Telephone support

  • At A Glance
  • Delivery and Returns

Zeta UV Flame Detector C/W Base

How much will it cost to deliver my order?

Standard delivery is 2-3 days from the date of despatch. Orders under £50 the postage is £4.95 but orders over £50 the postage is FREE (UK Mainland Only)

Next Working Day - £8.50 (Please note that the Next Working Day option is not available in all locations and is only available if all the items you are trying to order are in stock please check with sales for eligibility)

Read more...


What if I want to return my order?

We hope that you will be happy with your Locksonline purchase. However sometimes you may need to return a purchase. We we will happily refund or exchange purchases, provided it is within 7 days of delivery, in its original packaging and with proof of purchase.

Read more...

Flame detectors are available in 2 styles. A general purpose one which responds only to UV, and a combined UV and IR detector. The combined detector gives a higher immunity to false alarms caused by spurious UV sources, and is also available in explosion proof enclosure.

The development of the ZTFD101 ultra violet flame detector is based on over 10 years experience in the field of flame detection. The ZTFD101 is particularly suited in applications where flame can be expected to develop initially rather than smoke, due to the nature of the combustible materials such as camera films, video/audio/computer tapes , and petrochemical products (such as oil or petrol).

Features

The detector should be installed indoors, either on a ceiling or a wall. For maximum sensitivity the detector should see the side of the flame, but this is not always possible. Also avoid obstructions (including glass), as the detector is a line of sight device. Calculate the area of coverage of each device based on the height (or distance from risk area if wall mounted) and the cone of vision (120°). This detector works best when fed from a clean supply with minimal ripple.
Maintenance consists of ensuring the quartz sensor tube is kept clean and free from silicon, oil and grease. The detector should be functionally tested at regular intervals. Please note that this detector can give false alarms if exposed to spurious sources of UV, such as sparks, uncovered quarts halogen lights, or lightning.

• Low profile shape for UV detector
• The detector is solar blind and incorporates an electronic filter to eliminate unwanted alarms from naturally occurring phenomena.
• High immunity to Electrical noise & RF Interference.
• Fast response time.
• Supplied with its own base.
• Typically detects 25mm gas flame at 6 metres within 3 seconds.
• 120o cone of vision.
• Low Cost.